Growatt New Energy
Growatt New Energy MAC 60KTL3-X MV
MAC 50-70KTL3-X LV/MV
String inverter
Growatt New Energy MAC 60KTL3-X MV has a reviewed nominal AC active-power rating of 60000 W.
Deep comparison fields reviewedThis local comparison record does not approve module compatibility, string sizing, grid connection or electrical safety.
Documented source scope: Global / ROW. This is not a statement about your location or product availability.
Representative illustration — not the manufacturer’s exact hardware appearance.
Field-level provenance
Electrical specifications
Unknown means the field has not passed this exact-record integration review. It does not mean zero.
| AC output | |
|---|---|
| Rated AC active power | 60000 Wmanufacturer datasheet table row as labelled; no design inference Raw/footnote context: 60000W Official source ↗ · Output data (AC): Rated/AC nominal power Revision: 202305 · Checked 2026-10-02 |
| Maximum AC apparent output | 66600 VAmanufacturer datasheet table row as labelled; no design inference Raw/footnote context: 66600VA Official source ↗ · Output data (AC): Max. AC apparent power Revision: 202305 · Checked 2026-10-02 |
| Connection phases | 3Task10 exact-model evidence records phase as 'three_phase'; normalized to 3 connection phase(s). Identity/category source is official Growatt evidence; no grid approval inferred. Raw/footnote context: 50/60Hz (45-55Hz/55-65Hz) Official source ↗ · Task10 exact-model record invmfr_growatt|MAC 60KTL3-X MV|Global / ROW field 'phase'; official identity anchor: Official Growatt product page tied to the Task10 exact-model family/market identity. Revision: 202305 · Checked 2026-10-02 |
| PV input & tracking | |
| Independent MPPT trackers | 3manufacturer datasheet table row as labelled; no design inference Raw/footnote context: 3 Official source ↗ · Input data (DC): No. of MPP trackers Revision: 202305 · Checked 2026-10-02 |
| MPPT operating window minimum | 200 Vmanufacturer datasheet table row as labelled; no design inference; lower bound of the manufacturer MPPT operating range. Raw/footnote context: 200-1000V Official source ↗ · Input data (DC): MPP/MPPT voltage range Revision: 202305 · Checked 2026-10-02 |
| MPPT operating window maximum | 1000 Vmanufacturer datasheet table row as labelled; no design inference; upper bound of the manufacturer MPPT operating range. Raw/footnote context: 200-1000V Official source ↗ · Input data (DC): MPP/MPPT voltage range Revision: 202305 · Checked 2026-10-02 |
| DC operating voltage minimum | Unknown |
| DC operating voltage maximum | Unknown |
| Maximum PV input voltage | 1100 Vmanufacturer datasheet table row as labelled; no design inference Raw/footnote context: 1100V Official source ↗ · Input data (DC): Max. DC voltage Revision: 202305 · Checked 2026-10-02 |
| Maximum input current per tracker/input | 52 / 52 / 52 Amanufacturer datasheet table row as labelled; no design inference Raw/footnote context: 52A/52A/52A Official source ↗ · Input data (DC): Max. input current per MPP tracker Revision: 202305 · Checked 2026-10-02 |
| Maximum PV short-circuit current | 55 Amanufacturer datasheet table row as labelled; no design inference Raw/footnote context: 55 Official source ↗ · Input data (DC): Max. short-circuit current per MPP tracker Revision: 202305 · Checked 2026-10-02 |
| Efficiency & environment | |
| Maximum conversion efficiency | 98.8 %manufacturer datasheet table row as labelled; no design inference Raw/footnote context: 98.8% Official source ↗ · Efficiency: Max. efficiency Revision: 202305 · Checked 2026-10-02 |
| European efficiency | 98.5 %manufacturer datasheet table row as labelled; no design inference Raw/footnote context: 98.5% Official source ↗ · Efficiency: European efficiency Revision: 202305 · Checked 2026-10-02 |
| Operating ambient temperature minimum | -25 °Cmanufacturer datasheet table row as labelled; no design inference; lower ambient operating-temperature bound. Raw/footnote context: -25°C ... +60°C Official source ↗ · General data: Operating temperature range Revision: 202305 · Checked 2026-10-02 |
| Operating ambient temperature maximum | 60 °Cmanufacturer datasheet table row as labelled; no design inference; upper ambient operating-temperature bound. Raw/footnote context: -25°C ... +60°C Official source ↗ · General data: Operating temperature range Revision: 202305 · Checked 2026-10-02 |
| Enclosure protection | IP65manufacturer datasheet table row as labelled; no design inference Raw/footnote context: IP65 Official source ↗ · General data: Protection degree Revision: 202305 · Checked 2026-10-02 |
| Surge protection | Unknown |
| Warranty | |
| Warranty and eligibility | 5 years standard; 10 years optionalmanufacturer datasheet table row as labelled; no design inference Raw/footnote context: 5 years / 10 years; Yes/Optional Official source ↗ · General data: Warranty Revision: 202305 · Checked 2026-10-02 |
Comparison category basis
Official Task10/Growatt category identifies a PV inverter/string-type product; no microinverter or MLPE evidence is present.
Generic artwork is presentation-only and is not hardware, compatibility, dimension or electrical evidence.