Compare inverters.
Exact market specifications side by side, limited to one reviewed comparison category.
Comparison does not establish module compatibility, string sizing, grid approval or safety. W and VA remain separate ratings.
Hybrid / smart energy inverter
2 exact records
Edit selection
| Specification | GW100K07-ETCGoodWe Technologies Co., Ltd. · GermanyDeep comparison fields reviewed | GW100K-ETR-G10GoodWe Technologies Co., Ltd. · Global catalog (exact country/grid certificate not asserted)Deep comparison fields reviewed |
|---|---|---|
| AC output | ||
| Rated AC active power | 100000 WOn-grid nominal output power; exact source raw value '100 kW' kW. Converted exactly to website base unit; W and VA not interchanged. Official source ↗ | 100000 WOfficial manufacturer technical-table value for the exact model; no compatibility, grid, design or publication approval implied. Official source ↗ |
| Maximum AC apparent output | 110000 VAMax apparent power to utility grid; exact source raw value '110 kVA' kVA. Converted exactly to website base unit; W and VA not interchanged. Official source ↗ | 110000 VAOfficial maximum AC apparent output rating for the exact model; W and VA kept separate and model/market footnotes retained. Official source ↗ |
| Connection phases | 3Connection phase count bound to Task10 exact identity (three-phase); nominal wiring/voltage evidence retained. Official source ↗ | 3Connection phase count from official family/model description and exact identity (three-phase). Official source ↗ |
| PV input & tracking | ||
| Independent MPPT trackers | 2MPP trackers; exact model/market Task10 evidence reused. Official source ↗ | 10Official manufacturer technical-table value for the exact model; no compatibility, grid, design or publication approval implied. Official source ↗ |
| MPPT operating window minimum | 250 VMPPT operating range; endpoint of exact official range [250, 960], not the absolute DC limit. Official source ↗ | 160 VEndpoint of the official MPPT operating voltage range for the exact model; not the absolute DC limit. Official source ↗ |
| MPPT operating window maximum | 960 VMPPT operating range; endpoint of exact official range [250, 960], not the absolute DC limit. Official source ↗ | 1000 VEndpoint of the official MPPT operating voltage range for the exact model; not the absolute DC limit. Official source ↗ |
| DC operating voltage minimum | Unknown | Unknown |
| DC operating voltage maximum | Unknown | Unknown |
| Maximum PV input voltage | 1000 VPV max input voltage; exact model/market Task10 evidence reused. Official source ↗ | 1100 VOfficial manufacturer technical-table value for the exact model; no compatibility, grid, design or publication approval implied. Official source ↗ |
| Maximum input current per tracker/input | 100 AMax input current per MPPT; per-MPPT/input maximum, not total inverter current. Official source ↗ | 42 AOfficial maximum per-MPPT value for the exact model; not summed across trackers. Official source ↗ |
| Maximum PV short-circuit current | 125 AMax short circuit current per MPPT; per-MPPT/input maximum, not total inverter current. Official source ↗ | 55 AOfficial maximum per-MPPT value for the exact model; not summed across trackers. Official source ↗ |
| Efficiency & environment | ||
| Maximum conversion efficiency | 97.6 %Max efficiency; exact model/market Task10 evidence reused. Official source ↗ | 98.1 %Official manufacturer technical-table value for the exact model; no compatibility, grid, design or publication approval implied. Official source ↗ |
| European efficiency | 97.3 %European efficiency; exact model/market Task10 evidence reused. Official source ↗ | 97.7 %Official manufacturer technical-table value for the exact model; no compatibility, grid, design or publication approval implied. Official source ↗ |
| Operating ambient temperature minimum | -20 °COperating temp; >45°C derating; lower endpoint of exact official range [-20, 60]. Official source ↗ | -35 °COfficial manufacturer technical-table value for the exact model; no compatibility, grid, design or publication approval implied. Official source ↗ |
| Operating ambient temperature maximum | 60 °COperating temp; >45°C derating; upper endpoint of exact official range [-20, 60]. Official source ↗ | 60 °COfficial manufacturer technical-table value for the exact model; no compatibility, grid, design or publication approval implied. Official source ↗ |
| Enclosure protection | IP20Official enclosure ingress-protection rating; catalogue description only, not a safety or suitability approval. Official source ↗ | IP66Official enclosure ingress-protection rating; catalogue description only, not a safety or suitability approval. Official source ↗ |
| Surge protection | DC: Type II (Type I + II optional); AC: Type II (Type I + II optional)Official surge-protection configuration for this exact model family; optional enhancements are preserved verbatim where stated. Official source ↗ | DC: Type II (Type I + II optional); AC: Type IIOfficial surge-protection configuration for this exact model family; optional enhancements are preserved verbatim where stated. Official source ↗ |
| Warranty | ||
| Warranty and eligibility | Unknown | Unknown |