PUBLIC CATALOGUE • 632 comparison-ready inverter records. Incomplete identities are not shown.
← Choose inverters

Compare inverters.

Exact market specifications side by side, limited to one reviewed comparison category.

Comparison does not establish module compatibility, string sizing, grid approval or safety. W and VA remain separate ratings.

Hybrid / smart energy inverter 2 exact records
Edit selection
Inverter electrical comparison
SpecificationSBSE5.0-50SMA Solar Technology AG · Europe / ROWDeep comparison fields reviewedSUN-8K-SG05LP1-EU-SM2-PNingbo Deye Inverter Technology Co., Ltd. · Global / Europe (EU-labelled)Deep comparison fields reviewed
AC output
Rated AC active power5000 WAt 230 V, 50 Hz; footnote 2 limits output to 4600 W / 4600 VA under VDE-AR-N 4105.
Official source ↗
8000 Wrated AC input/output active power
Official source ↗
Maximum AC apparent output5000 VAAt 230 V, 50 Hz; footnote 2 limits output to 4600 W / 4600 VA under VDE-AR-N 4105.
Official source ↗
8800 VAmaximum AC input/output apparent power
Official source ↗
Connection phases1Single-phase hybrid description on PDF page 1.
Official source ↗
1Official current product family identifies exact model as single-phase.
Official source ↗
PV input & tracking
Independent MPPT trackers3Manufacturer rated specification for this exact model and market; no compatibility approval.
Official source ↗
2MPP trackers
Official source ↗
MPPT operating window minimum60 VManufacturer rated specification for this exact model and market; no compatibility approval.
Official source ↗
150 VMPPT operating range
Official source ↗
MPPT operating window maximum480 VManufacturer rated specification for this exact model and market; no compatibility approval.
Official source ↗
425 VMPPT operating range
Official source ↗
DC operating voltage minimumUnknownUnknown
DC operating voltage maximumUnknownUnknown
Maximum PV input voltage600 VManufacturer rated specification for this exact model and market; no compatibility approval.
Official source ↗
500 Vmaximum PV input voltage
Official source ↗
Maximum input current per tracker/input15 AEach PV input A/B/C; do not add battery input current.
Official source ↗
32 / 32 Aper-MPPT operating PV input current
Official source ↗
Maximum PV short-circuit current30 AUp to 30 A per input A/B/C; sum across all inputs must not exceed 60 A.
Official source ↗
48 / 48 Aper-MPPT short-circuit current
Official source ↗
Efficiency & environment
Maximum conversion efficiency98.1 %Manufacturer rated specification for this exact model and market; no compatibility approval.
Official source ↗
97.6 %maximum efficiency
Official source ↗
European efficiencyUnknown96.5 %Euro efficiency
Official source ↗
Operating ambient temperature minimum-25 °CAmbient operating range, with derating.
Official source ↗
-40 °Coperating temperature and derating threshold; derating above 45 °C
Official source ↗
Operating ambient temperature maximum60 °CAmbient operating range, with derating.
Official source ↗
60 °Coperating temperature and derating threshold; derating above 45 °C
Official source ↗
Enclosure protectionIP65Manufacturer rated specification for this exact model and market; no compatibility approval.
Official source ↗
IP65Official current product page enclosure rating.
Official source ↗
Surge protectionDC Type II external SPD optionalManufacturer rated specification for this exact model and market; no compatibility approval.
Official source ↗
Type II (DC), Type II (AC)Official current product page surge-protection level.
Official source ↗
Warranty
Warranty and eligibility5 years standard; 10 years with registration within 30 days; 15/20 years optional. Manufacturer warranty conditions apply.Manufacturer rated specification for this exact model and market; no compatibility approval.
Official source ↗
5 years / up to 10 years*Official current product page; extension availability is country/region dependent and subject to manufacturer policy.
Official source ↗