PUBLIC CATALOGUE • 632 comparison-ready inverter records. Incomplete identities are not shown.
← Choose inverters

Compare inverters.

Exact market specifications side by side, limited to one reviewed comparison category.

Comparison does not establish module compatibility, string sizing, grid approval or safety. W and VA remain separate ratings.

Hybrid / smart energy inverter 3 exact records · Differences include rating conditions and scope.
Edit selection
Inverter electrical comparison
SpecificationH3-12.0-SmartFox ESS · Global / ROW official siteDeep comparison fields reviewedGW10KL-ETGoodWe Technologies Co., Ltd. · AustraliaDeep comparison fields reviewedH3-9.9-SmartFox ESS · Global / ROW official siteDeep comparison fields reviewed
AC output
Rated AC active power12000 Wnominal active AC output; scope: AC output; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit W
Official source ↗
technical table Nominal AC Power
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

10000 Wnominal/rated active power; exact source raw value '10000' W. Converted exactly to website base unit; W and VA not interchanged.
Source unit W
Official source ↗
Technical Data > AC nominal/rated output power
Revision GoodWe-Single page-20250417-AU-V2.1 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

9900 Wnominal active AC output; scope: AC output; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit W
Official source ↗
technical table Nominal AC Power
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

Maximum AC apparent output13200 VAmaximum apparent AC output for stated market; scope: AC output; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit VA
Official source ↗
technical table Max. Apparent AC Power; Belgium footnote where applicable
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

11000 VAmaximum apparent power; exact source raw value '11000' VA. Converted exactly to website base unit; W and VA not interchanged.
Source unit VA
Official source ↗
Technical Data > Max. apparent power to utility grid
Revision GoodWe-Single page-20250417-AU-V2.1 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

9900 VAmaximum apparent AC output for stated market; scope: AC output; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit VA
Official source ↗
technical table Max. Apparent AC Power; Belgium footnote where applicable
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

Connection phases3Official exact-model/family phase identity: three-phase. For North-American split-phase, the literal split-phase descriptor is retained rather than converted to a false phase count. No grid-approval inference.
Official source ↗
p.2 AC OUTPUT — Rated Grid Voltage 400/230 V; 380/220 V, 3L/N/PE; exact model column
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

3Connection phase count bound to Task10 exact identity (Three phase); nominal wiring/voltage evidence retained.
Official source ↗
Technical Data > Nominal output voltage
Revision GoodWe-Single page-20250417-AU-V2.1 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

3Official exact-model/family phase identity: three-phase. For North-American split-phase, the literal split-phase descriptor is retained rather than converted to a false phase count. No grid-approval inference.
Official source ↗
p.2 AC OUTPUT — Rated Grid Voltage 400/230 V; 380/220 V, 3L/N/PE; exact model column
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

PV input & tracking
Independent MPPT trackers3independent MPP trackers; scope: inverter; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Official source ↗
technical table No. of MPP Trackers
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

2count; exact model/market Task10 evidence reused.
Official source ↗
Technical Data > Number of MPPT trackers
Revision GoodWe-Single page-20250417-AU-V2.1 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

3independent MPP trackers; scope: inverter; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Official source ↗
technical table No. of MPP Trackers
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

MPPT operating window minimum120 Voperating MPPT range; scope: MPPT; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit V
Official source ↗
technical table MPPT Voltage Range; canonical min bound from source range
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

200 Voperating range; endpoint of exact official range [200, 850], not the absolute DC limit.
Source unit V
Official source ↗
Technical Data > MPPT operating voltage range
Revision GoodWe-Single page-20250417-AU-V2.1 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

120 Voperating MPPT range; scope: MPPT; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit V
Official source ↗
technical table MPPT Voltage Range; canonical min bound from source range
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

MPPT operating window maximum950 Voperating MPPT range; scope: MPPT; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit V
Official source ↗
technical table MPPT Voltage Range; canonical max bound from source range
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

850 Voperating range; endpoint of exact official range [200, 850], not the absolute DC limit.
Source unit V
Official source ↗
Technical Data > MPPT operating voltage range
Revision GoodWe-Single page-20250417-AU-V2.1 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

950 Voperating MPPT range; scope: MPPT; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit V
Official source ↗
technical table MPPT Voltage Range; canonical max bound from source range
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

DC operating voltage minimumUnknownUnknownUnknown
DC operating voltage maximumUnknownUnknownUnknown
Maximum PV input voltage1000 Vmaximum DC voltage; scope: PV input; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit V
Official source ↗
technical table Max. DC Voltage; note max operating 950V
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

1000 Vmaximum; exact model/market Task10 evidence reused.
Source unit V
Official source ↗
Technical Data > PV max. input voltage
Revision GoodWe-Single page-20250417-AU-V2.1 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

1000 Vmaximum DC voltage; scope: PV input; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit V
Official source ↗
technical table Max. DC Voltage; note max operating 950V
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

Maximum input current per tracker/input20 / 20 / 20 Amaximum current by MPPT; scope: MPPT1/2/3; raw source cell retained: 20/20/20; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit A
Official source ↗
technical table Max. MPPT Current
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

22 Aper-MPPT maximum; exact per-MPPT sequence [12.5, 22.0]; scalar stores the maximum listed per-MPPT value, not a sum.
Source unit A
Official source ↗
Technical Data > Max. input current per MPPT
Revision GoodWe-Single page-20250417-AU-V2.1 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

20 / 20 / 20 Amaximum current by MPPT; scope: MPPT1/2/3; raw source cell retained: 20/20/20; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit A
Official source ↗
technical table Max. MPPT Current
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

Maximum PV short-circuit current25 / 25 / 25 Amaximum short-circuit current by MPPT; scope: MPPT1/2/3; raw source cell retained: 25/25/25; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit A
Official source ↗
technical table Max. Short-circuit Current
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

27.6 Aper-MPPT maximum; exact per-MPPT sequence [15.2, 27.6]; scalar stores the maximum listed per-MPPT value, not a sum.
Source unit A
Official source ↗
Technical Data > Max. short-circuit current per MPPT
Revision GoodWe-Single page-20250417-AU-V2.1 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

25 / 25 / 25 Amaximum short-circuit current by MPPT; scope: MPPT1/2/3; raw source cell retained: 25/25/25; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit A
Official source ↗
technical table Max. Short-circuit Current
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

Efficiency & environment
Maximum conversion efficiency97.9 %maximum conversion efficiency; scope: efficiency; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit %
Official source ↗
technical table Max. Efficiency
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

97.6 %maximum efficiency; exact model/market Task10 evidence reused.
Source unit %
Official source ↗
Technical Data > Max. efficiency
Revision GoodWe-Single page-20250417-AU-V2.1 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

97.9 %maximum conversion efficiency; scope: efficiency; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit %
Official source ↗
technical table Max. Efficiency
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

European efficiency97.2 %European efficiency; scope: efficiency; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit %
Official source ↗
technical table European Efficiency
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

96.8 %European efficiency; exact model/market Task10 evidence reused.
Source unit %
Official source ↗
Technical Data > European efficiency
Revision GoodWe-Single page-20250417-AU-V2.1 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

97.2 %European efficiency; scope: efficiency; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit %
Official source ↗
technical table European Efficiency
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

Operating ambient temperature minimum-25 °Cambient range and derating threshold; scope: environment; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit °C
Official source ↗
technical table Operating Temperature; canonical min bound from source range
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

-35 °Coperating range; lower endpoint of exact official range [-35, 60].
Source unit °C
Official source ↗
Technical Data > Operating temperature range
Revision GoodWe-Single page-20250417-AU-V2.1 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

-25 °Cambient range and derating threshold; scope: environment; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit °C
Official source ↗
technical table Operating Temperature; canonical min bound from source range
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

Operating ambient temperature maximum60 °Cambient range and derating threshold; scope: environment; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit °C
Official source ↗
technical table Operating Temperature; canonical max bound from source range
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

60 °Coperating range; upper endpoint of exact official range [-35, 60].
Source unit °C
Official source ↗
Technical Data > Operating temperature range
Revision GoodWe-Single page-20250417-AU-V2.1 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

60 °Cambient range and derating threshold; scope: environment; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Source unit °C
Official source ↗
technical table Operating Temperature; canonical max bound from source range
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

Enclosure protectionIP65ingress protection rating; scope: enclosure; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Official source ↗
technical table Ingress Protection
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

IP66Official enclosure ingress-protection rating; catalogue description only, not a safety or suitability approval.
Official source ↗
Official technical data / Ingress Protection Rating; exact family/model applicability for GW10KL-ET.
Revision GoodWe-Single page-20250417-AU-V2.1 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

IP65ingress protection rating; scope: enclosure; Exact model/market manufacturer evidence; no compatibility, string-sizing, grid or safety approval.
Official source ↗
technical table Ingress Protection
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

Surge protectionDC Type II / AC Type IIManufacturer protection table; optional qualifiers retained where stated. Decorative/catalogue use only; no safety approval.
Official source ↗
p.2 PROTECTION — DC/AC Surge Protection row
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

DC: Type III; AC: Type IIIOfficial surge-protection configuration for this exact model family; optional enhancements are preserved verbatim where stated.
Official source ↗
Official Protection table / surge-protection rows for family containing exact model GW10KL-ET.
Revision GoodWe-Single page-20250417-AU-V2.1 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

DC Type II / AC Type IIManufacturer protection table; optional qualifiers retained where stated. Decorative/catalogue use only; no safety approval.
Official source ↗
p.2 PROTECTION — DC/AC Surge Protection row
Revision V2.0 · Checked 2026-10-02

Source check overdue · Last checked 2026-11-17T21:53:45.238651+00:00

Warranty
Warranty and eligibilityUnknownUnknownUnknown